Please use this identifier to cite or link to this item: https://repositorio.ufpa.br/jspui/handle/2011/13566
metadata.dc.type: Dissertação
Issue Date: 7-Apr-2021
metadata.dc.creator: CARVALHO, Franklin Barbosa de
metadata.dc.description.affiliation: Instituto de Educação Marchelli de Almeida Crispim
metadata.dc.contributor.advisor1: NASCIMENTO, Manoel Henrique Reis
Title: Metodologia de aterramento em linha de transmissão em ocorrência alternada 550 KV na Amazônia – um estudo de caso
Other Titles: Grounding methodology on a 550 KV power transmission line in the Amazon - a case study
Citation: CARVALHO, Franklin Barbosa de. Metodologia de aterramento em linha de transmissão em corrente alternada 550 KV na Amazônia – um estudo de caso. Orientador: Manoel Henrique Reis Nascimento. 2021. 47 f. Dissertação (Mestrado em Engenharia de Processos) - Programa de Pós-Graduação em Engenharia de Processos, Instituto de Tecnologia, Universidade Federal do Pará, Belém, 2021. Disponível em: http://repositorio.ufpa.br/jspui/handle/2011/13566. Acesso em:.
metadata.dc.description.resumo: As descargas atmosféricas são de grande importância para o setor elétrico, sendo frequentemente responsáveis por desligamentos de linhas de transmissão, as quais podem desencadear uma sequência de eventos que levem o sistema elétrico interligado ao colapso. O objetivo deste trabalho é propor uma nova metodologia para correção das resistências de aterramento da linha de transmissão LT Oriximiná/Silves CD 550kV de energia elétrica na Amazônia prospectando reduzir as ocorrências de desligamento por descarga disruptiva de retorno, ou backflashover mitigando os danos causados ao sistema elétrico, considerando os fatores de custo de implementação, viabilidade técnica ambiental, abrangência da solução para demais estrutura da linha, percentual de redução da implementação, concluiu-se que a solução mais adequada para implementar uma solução mais robusta de aterramento nas torres da linha de transmissão é a solução 03 testada na torre 585 com redução de 66,98%.
Abstract: Lightning strikes are of great importance for the electricity sector, being frequently responsible for disconnections of transmission lines, which can trigger a sequence of events that lead to the interconnected electrical system to collapse. The objective of this work is to propose a new methodology to correct the grounding resistances of the LT Oriximiná / Silves CD 550kV electric power transmission line in the Amazon aiming to reduce the occurrences of shutdown by disruptive return discharge, or backflashover, mitigating the damages caused to the system. electrical, considering the implementation cost factors, environmental technical feasibility, abruptness of the solution for other line structures, percentage of implementation reduction, it was concluded that the most adequate solution to implement a more robust grounding solution in the towers of the line transmission is the 03 solution tested on the 585 tower with a 66.98% reduction.
Keywords: Descargas atmosféricas
Aterramento
Linha de Transmissão, desligamentos
Atmosferic discharges
Grounding
Transmission Line, disconnections
metadata.dc.subject.areadeconcentracao: ENGENHARIA DE PROCESSOS
metadata.dc.subject.linhadepesquisa: PROCESSOS INDUSTRIAIS
metadata.dc.subject.cnpq: CNPQ::ENGENHARIAS::ENGENHARIA DE PRODUCAO
metadata.dc.publisher.country: Brasil
Publisher: Universidade Federal do Pará
metadata.dc.publisher.initials: UFPA
metadata.dc.publisher.department: Instituto de Tecnologia
metadata.dc.publisher.program: Programa de Pós-Graduação em Engenharia de Processos
metadata.dc.rights: Acesso Aberto
Attribution-NonCommercial-NoDerivs 3.0 Brazil
metadata.dc.source.uri: Disponível na internet via correio eletrônico: bibliotecaitec@ufpa.br
Appears in Collections:Dissertações em Engenharia de Processos (Mestrado) - PPGEP/ITEC

Files in This Item:
File Description SizeFormat 
Dissertacao_MetodologiaAterramentoLinha.pdf1,14 MBAdobe PDFView/Open


This item is licensed under a Creative Commons License Creative Commons