Por favor, use este identificador para citar o enlazar este ítem: https://repositorio.ufpa.br/jspui/handle/2011/13566
Tipo: Dissertação
Fecha de publicación : 7-abr-2021
Autor(es): CARVALHO, Franklin Barbosa de
metadata.dc.description.affiliation: Instituto de Educação Marchelli de Almeida Crispim
Primer Orientador: NASCIMENTO, Manoel Henrique Reis
Título : Metodologia de aterramento em linha de transmissão em ocorrência alternada 550 KV na Amazônia – um estudo de caso
Otros títulos : Grounding methodology on a 550 KV power transmission line in the Amazon - a case study
Citación : CARVALHO, Franklin Barbosa de. Metodologia de aterramento em linha de transmissão em corrente alternada 550 KV na Amazônia – um estudo de caso. Orientador: Manoel Henrique Reis Nascimento. 2021. 47 f. Dissertação (Mestrado em Engenharia de Processos) - Programa de Pós-Graduação em Engenharia de Processos, Instituto de Tecnologia, Universidade Federal do Pará, Belém, 2021. Disponível em: http://repositorio.ufpa.br/jspui/handle/2011/13566. Acesso em:.
Resumen: As descargas atmosféricas são de grande importância para o setor elétrico, sendo frequentemente responsáveis por desligamentos de linhas de transmissão, as quais podem desencadear uma sequência de eventos que levem o sistema elétrico interligado ao colapso. O objetivo deste trabalho é propor uma nova metodologia para correção das resistências de aterramento da linha de transmissão LT Oriximiná/Silves CD 550kV de energia elétrica na Amazônia prospectando reduzir as ocorrências de desligamento por descarga disruptiva de retorno, ou backflashover mitigando os danos causados ao sistema elétrico, considerando os fatores de custo de implementação, viabilidade técnica ambiental, abrangência da solução para demais estrutura da linha, percentual de redução da implementação, concluiu-se que a solução mais adequada para implementar uma solução mais robusta de aterramento nas torres da linha de transmissão é a solução 03 testada na torre 585 com redução de 66,98%.
Resumen : Lightning strikes are of great importance for the electricity sector, being frequently responsible for disconnections of transmission lines, which can trigger a sequence of events that lead to the interconnected electrical system to collapse. The objective of this work is to propose a new methodology to correct the grounding resistances of the LT Oriximiná / Silves CD 550kV electric power transmission line in the Amazon aiming to reduce the occurrences of shutdown by disruptive return discharge, or backflashover, mitigating the damages caused to the system. electrical, considering the implementation cost factors, environmental technical feasibility, abruptness of the solution for other line structures, percentage of implementation reduction, it was concluded that the most adequate solution to implement a more robust grounding solution in the towers of the line transmission is the 03 solution tested on the 585 tower with a 66.98% reduction.
Palabras clave : Descargas atmosféricas
Aterramento
Linha de Transmissão, desligamentos
Atmosferic discharges
Grounding
Transmission Line, disconnections
metadata.dc.subject.areadeconcentracao: ENGENHARIA DE PROCESSOS
metadata.dc.subject.linhadepesquisa: PROCESSOS INDUSTRIAIS
CNPq: CNPQ::ENGENHARIAS::ENGENHARIA DE PRODUCAO
País: Brasil
Editorial : Universidade Federal do Pará
Sigla da Instituição: UFPA
Instituto: Instituto de Tecnologia
Programa: Programa de Pós-Graduação em Engenharia de Processos
metadata.dc.rights: Acesso Aberto
Attribution-NonCommercial-NoDerivs 3.0 Brazil
metadata.dc.source.uri: Disponível na internet via correio eletrônico: bibliotecaitec@ufpa.br
Aparece en las colecciones: Dissertações em Engenharia de Processos (Mestrado) - PPGEP/ITEC